Support
micro emf models magnetic and electric fields around power circuits and earth wires. There are two kinds of model: an EMF model for the magnetic field, and an electric field model. Tap + on the models list to create either one.
Getting Started: Magnetic Field Models
- Create a model: Tap + and choose EMF Model. Set the frequency and soil resistivity, and the measurement band: the height above ground and the range of positions to estimate the field at.
- Add circuits: Add each power circuit with its three phase wires and, if needed, a neutral wire. Enter the load as power (MW and MVAr) or as phase currents.
- Add earth wires: Add earth wires with their position, radius and resistance. The app estimates the current induced in each one.
- View results: The results show the maximum field, a field profile chart in µT or mG, the induced earth wire currents and a full data table.
- Export results: Share the results as PDF, CSV, HTML or JSON.
Getting Started: Electric Field Models
- Create a model: Tap + and choose Electric Field Model. Set the frequency, the reference temperature and conductor temperature (used for sag), and the measurement band.
- Add conductors: Add one conductor for each phase. Enter its x position, support height, radius, phase voltage in kV (phase to earth, for example 190.5 kV on a 330 kV line) and phase angle.
- Set the sag: Enter the sag at the reference temperature. The app adjusts it for thermal expansion at the conductor temperature and lowers the conductor by that amount from its support height. Leave sag at 0 to model the conductor at support height.
- Add bundles: For bundled conductors, set the number of subconductors (up to 8) and the bundle spacing. The app places the subconductors evenly around a circle centred on the conductor position, with the bundle spacing as its diameter. The radius is the radius of each subconductor.
- Add earth wires: Add a conductor and turn on Earth Wire. Earth wires are modelled at earth potential when estimating the field, and the results also show the voltage induced on each one.
- Calculate: The results show the maximum electric field and where it occurs, a profile chart and a data table.
- Export results: Share the results as CSV.
Reading the Electric Field Profile
- The chart plots the RMS of the vertical electric field (Ey RMS) in V/m at the measurement height, across the measurement band.
- The maximum shows the highest value in the band, its x position and the measurement height.
- A double circuit line often gives two peaks, one on each side of the centre line. Phase arrangement, conductor height and sag all change the shape of the profile.
- Use a smaller step size to see more detail around the peaks.
Frequently Asked Questions
What does the free version include?
The free version includes 1 model (magnetic and electric field models count together), 1 circuit per model and no earth wires. A Pro subscription, monthly or yearly with a 14-day free trial, unlocks everything.
How many circuits can I model?
A magnetic field model can have up to 30 circuits, each with three phase wires and an optional neutral wire.
What frequencies are supported?
You can set each model to 50 Hz or 60 Hz.
Can I use power-based or current-based inputs?
Yes. For each circuit in a magnetic field model you can enter power (MW and MVAr) or the phase currents directly.
Does my data sync across devices?
Yes. micro emf uses iCloud to sync your models across iPhone and iPad, and your models are available offline in the field.
What export formats are available?
Magnetic field results export to PDF, CSV, HTML and JSON. Electric field results export to CSV.
How are earth wire induced currents calculated?
Earth wire calculations use impedance matrices based on Carson's equations, taking account of soil resistivity and wire geometry.
What voltage do I enter for an electric field conductor?
Enter the phase-to-earth voltage in kV, which is the line voltage divided by √3. Set the phase angle for each phase, for example 0°, -120° and 120°.
Why does the app say a conductor has an effective height ≤ 0 after sag adjustment?
The sag, after the temperature adjustment, is equal to or greater than the support height. Check the support height, the sag and the two temperatures for that conductor.
Tips for Best Results
- Check wire and conductor positions in the diagram view before calculating
- Use consistent units throughout your model
- For complex transmission lines, break them into logical circuit groups
- Export to CSV for further analysis in a spreadsheet